Submission incomplete:
Scope: The verification report does not provide an assessment of the compliance with EB 52 Annex 60 'Guidelines for assessing compliance with the calibration frequency requirements' for the calibration delay. (VVM v.1.2 para 184 (a) (ii) & EB 52 Annex 60)
Issue: The calibration information presented on page 15 of the verification report is not consistent with that of the monitoring report (page 8). The calibration dates of meters 681 and 682 do not match. Further, the spreadsheet (Sheet "Corrected net generation") does not display the corrected data for the meter 682.