Submission incomplete:
Scope: The verification report does not provide an assessment on whether the calibration of measuring equipments was conducted at a frequency specified in applied monitoring methodology or EB guidance if applicable, and/or the monitoring plan? (VVM v.1.2 para 184 (a) (ii) & EB 52 Annex 60)
Issue: The DOE is required to clarify how the monitoring has been carried out in accordance with the registered monitoring plan as the accuracy class of the meters used to measure the electricity import is 1.0 whereas the registered monitoring plan (PDD (page 29) states that the tolerance of the installed model is class 0.5 (active power)
Scope: The verification report does not provide an assessment on whether the calibration of measuring equipments was conducted at a frequency specified in applied monitoring methodology or EB guidance if applicable, and/or the monitoring plan? (VVM v.1.2 para 184 (a) (ii) & EB 52 Annex 60)
Issue: The DOE is required to clarify how the monitoring has been carried out in accordance with the registered monitoring plan as the accuracy class of the meters used to measure the electricity import is 1.0 whereas the registered monitoring plan (PDD (page 29) states that the tolerance of the installed model is class 0.5 (active power)