Submission incomplete:
1: DOE's verification statement confirming whether the check meters are in compliance of the calibration frequency is missing -
The DOE is requested to confirm whether the check meters used to monitor electricity exported to the grid are duly calibrated during the monitoring period.

2: Discrepancy in accuracy class of main and check meter in the monitoring report and verification report -
The monitoring report on page 12 of 18 mentions accuracy class of main and check meter as 0.5 while the verification report on page 13 of 24 mentions the accuracy class for these meters as 0.2. The DOE is requested to confirm the actual accuracy class of the main and check meters installed at the project site.