Submission incomplete:
Scope: The verification report does not provide an assessment on whether the calibration of measuring equipments was conducted at a frequency specified in applied monitoring methodology or EB guidance if applicable, and/or the monitoring plan (VVS v2, para 243)
Issue: "The DOE (p 16) states that "A delay of 5 days has occurred in the calibration of energy meters at Line 1 and Line 2 at substation meters. Accordingly PP has adjusted the value of transmission loss by applying maximum permissible error of the meter for the concerning month as per § 238 of VVS. The verification team confirms that the error has been applied correctly and conservatively." Further information is required by the DOE on how it verified the delayed calibration as per para 238 a) and b) of VVSs as the validation report did not contain information on checking "the results of the delayed calibration test".