Submission incomplete:
Scope: The verification report does not contain information on all CARs, CLs and FARs and/or provide an assessment and close out of any CARs, CLs or FARs issued. (VVM v.1.2 para 192, 194)
Issue:The DOE (p. 8) states that "during the site visit it was observed that a meter (serial number IP6H48) was installed inside the power house. Meter IP6H48 is mono directional and it is used for measuring the electricity imported from a 13.8 kV OHTL." However, the monitoring plan of the registered PDD does not include the electricity import from the 13.8 kV. Further information is required by the DOE on why it did not raise a FAR to revise the monitoring plan to include the monitoring of the electricity import as the monitoring of this parameter is required to confirm para 77 of VVM."