Submission incomplete:
1: Scope: The spreadsheet does not contain all parameters required to be monitored and/or reported at the intervals required by the monitoring plan and the applied methodology.
Issue: The spreadsheet does not contain the parameters Tflare (Temperature in the exhaust gas of the flare) and ηflare (Efficiency of open and enclosed flare).

2: Scope: The verification report does not provide an assessment on whether the calibration of measuring equipments was conducted at a frequency specified in applied monitoring methodology or EB guidance if applicable, and/or the monitoring plan (VVS v2, para 243)
Issue: The verification report, page 24 indicates that the calibration of the biogas analyser was carried out by an accredited person or institution in accordance with the manufacturer’s specification for the calibration interval which is twice a year. However, the DOE has not provided information on the relevant accreditation for the calibrations carried out on on 7 June 2012, 17 September 2012 and 24 November 2012. Please refer to the CDM project standard, paragraph 97 (c).