Submission incomplete:
1: VVS-PA Para 365
As per the registered PDD, monitoring report and the verification report, the calibration frequency of all ABT meters and Yard meters is once in three years. The calibration dates of the ABT meter at GETCO Substation are mentioned as 23/03/2015 and 19/03/2018. The monitoring period considered for this submission is 01/08/2013 to 31/12/2020. DOE is therefore requested to explain, how it confirmed that meter was calibrated between period 01/08/2013 to 23/03/2015 as no details on calibration have been provided in the monitoring report or the verification report. Refer Para 365 of VVS-PA, version 3.0.
2: VVS-PA Para 374(b)
As per the registered PDD, net electricity supplied to the NEWNE grid by project activity will be cross checked against the invoice raised by the PP towards the Discom. However, no cross-check mechanism has been discussed in the monitoring report or the verification report. The DOE is therefore requested to clarify how it cross-checked the reported data for net electricity supplied. Refer Para 374(b) of VVS-PA, version 3.0.
1: VVS-PA Para 365
As per the registered PDD, monitoring report and the verification report, the calibration frequency of all ABT meters and Yard meters is once in three years. The calibration dates of the ABT meter at GETCO Substation are mentioned as 23/03/2015 and 19/03/2018. The monitoring period considered for this submission is 01/08/2013 to 31/12/2020. DOE is therefore requested to explain, how it confirmed that meter was calibrated between period 01/08/2013 to 23/03/2015 as no details on calibration have been provided in the monitoring report or the verification report. Refer Para 365 of VVS-PA, version 3.0.
2: VVS-PA Para 374(b)
As per the registered PDD, net electricity supplied to the NEWNE grid by project activity will be cross checked against the invoice raised by the PP towards the Discom. However, no cross-check mechanism has been discussed in the monitoring report or the verification report. The DOE is therefore requested to clarify how it cross-checked the reported data for net electricity supplied. Refer Para 374(b) of VVS-PA, version 3.0.
Offset now: visit the United Nations Carbon Offset Platform
Connect with us: