Submission incomplete:
VVS-PA, paragraph 366:
The DOE has mentioned that the meters with HTSC numbers 3769, 3770, 3772, 3773, 3774, 3775, 3776, 3777, 3778, 3789, 3790 and 3791 had a delayed calibration from period 03/11/2017 to 27/11/2017, and hence the error factor – 0.2% is applied for export values and +0.2% for import and transmission loss values. However, it is observed from pages 19-21 of the verification report that the calibrations conducted in 2017 are for the new meters. The DOE is requested to explain how this approach is in accordance with paragraph 366 of VVS-PA, as there is no information when the delayed calibration test of the old meters was carried out and what was the result of the delayed calibration test of the old meters.